Reference Publication: Parker, D., Fairey, P., McCluney, R., Gueymard, C., Stedman, T., McIlvaine, J., "Rebuilding For Efficiency: Improving the Energy Use of Reconstructed Residences in South Florida", Prepared for U.S. Department of Energy, Florida Energy Office, and Florida Power & Light Company, FSEC-CR-562-92, December 1992. Disclaimer: The views and opinions expressed in this article are solely those of the authors and are not intended to represent the views and opinions of the Florida Solar Energy Center. |
REBUILDING
FOR EFFICIENCY:
Improving the Energy Use of Reconstructed
Residences in South Florida
Danny
Parker, Philip Fairey, Ross McCluney,
Chris Gueymard, Ted Stedman, and Janet McIlvaine
Florida
Solar Energy Center (FSEC)
FSEC-CR-562-92
Executive Summary
On August 24th, 1992, Hurricane Andrew devastated a large part of South Dade County in Florida. With over 35,000 homes to be rebuilt, there is interest in seeing if these reconstructed residences can be made more energy-efficient.
This report provides a comprehensive assessment of potential energy efficiency improvements for both new and existing homes in South Florida. Over forty energy-efficiency measures were considered in the analysis. Many homes in the effected zone experienced damage to their windows, roofs and the surrounding landscape. As a result, the analysis closely examined options associated with these design aspects. All major end-uses of electricity were considered: space cooling and heating, water heating, refrigeration, lighting and other appliances.
Our research considered both the technical feasibility of available methods to save energy as well as the economics of the various options that are available. Optimization analysis was used to choose superior combinations of energy-efficiency measures that will provide maximum energy savings at the lowest possible cost. The study used a combination of monitoring studies and simulation analysis to determine the effectiveness of the various measures.
Results of the analysis showed that while it was technically feasible to reduce household electricity use in South Florida homes by 73 - 84%, the economically cost-effective savings ranged from 39% - 48 %. A group of economically superior measures were identified during the course of the analysis. These included the following improvements beyond the current energy code:
Envelope:
Heating and Cooling System:
Water Heating:
Appliances:
The identified package of measures for new construction was estimated to potentially reduce annual electricity consumption in rebuilt homes by 39% or 5,350 kWh at an initial cost of about $3,000. Summer utility coincident peak loads were predicted to drop by 1.5 kW-- about 37% lower than conventional new homes. Annual savings were calculated at approximately $430 with a seven year payback. The after-tax rate-of-return from this level of savings is very favorable at 14% in real terms. The package was estimated to save utility electrical generation at a cost of less than half that of current retail residential electricity prices. Savings for existing homes were predicted to be even higher (7,100 annual kWh), mainly due to the large potential improvements available from improving existing air conditioner efficiencies.
Regardless of the large magnitude of the identified savings potential, our analysis finds that there is still considerable uncertainty associated with a number of the analyzed measures. The study concludes that the certainty of the estimates and the composition of the savings packages may be considerably improved with a well-designed experimental study. We propose a research project with approximately 400 homes (200 control, 200 experimental) for the South Florida area. It is recommended that such a pilot demonstration project be undertaken at the earliest opportunity.
Appendices:
Appendix A: Monitored Residential
Building Energy Use in Florida
Appendix B: Analysis of Energy Losses
of Thermal Distribution System
Appendix C: Collected Cost Data for
Analysis
Appendix D: Window Selection Guidelines
for South Florida Residences
Appendix E: Reflective Roof Research
at FSEC
Appendix F: Appliance and Internal
Load Profiles
Appendix G: Economic Criteria for Analysis
Appendix H: Sample DOE
2.1D Input and Output for Analysis (pdf)
1. Introduction
On August 24th, 1992, Hurricane Andrew exacted tremendous physical devastation on the South Florida area. With top wind gusts of nearly 170 mph the class four storm was one of the most destructive hurricanes of the century. Cutting a 25-mile wide path of destruction across the suburbs of South Miami, at least 85,000 buildings in the area were severely damaged. Estimates show that some 34,000 homes will have to be replaced (WWR, 1992). Many more buildings experienced varying degrees of repairable damage. Many of the structures were single family residences in the communities of Kendall, South Miami, Homestead and Florida City. Over $7 billion in insured losses were sustained (ENR, 1992). Total damages are estimated at approximately $20 billion. Improvements in the code review and inspection process and hurricane resistance of construction methods have justifiably been of the greatest immediate concern (RSI, 1992; Miami Herald, 1992). Implications for structural performance of building materials has been recently covered in a research publication by the American Plywood Association (Keith and Rose, 1992).

Figure 1: Hurricane Andrew slams into Florida at 7 AM,
August 24th,
photographed by the infra-red camera aboard the GOES-7 satellite.
Color is proportional to atmospheric heat content. The eye of
the
storm is clearly visible over Homestead. (U.S. Weather Service)
However, since the storm, there has been a desire to see if something positive might be accomplished in response to the disaster. Organizations such as We Will Rebuild have already begun an encouraging effort to rejuvenate stricken neighborhoods. One emerging idea is that the new communities might incorporate greater energy efficiency in their reconstruction. In this fashion, the rebuilt homes might become a flagship for energy efficiency potential for residential buildings in the rest of the state.
This study provides a preliminary examination of the various options that are available to improve the energy efficiency of South Florida's residential buildings. Each energy end-use in homes is examined: space cooling and heating, appliances, water heating and amenities. The primary objective is to identify and quantify the savings available from various measures as well as their cost and performance.
The source for the developed information is a combination of monitoring studies, simulation analysis and calculation. A detailed building energy simulation, DOE 2.1D, was used for the analysis of cooling and heating options. Where possible, results were compared to existing field studies to establish the credibility of the results. Measurements and performance data are available for most of the other considered options. Where disputes or differences exist with respect to cost or savings, a range of potentials were examined or conservative assumptions were adopted.
The analysis considered two major building types:
The analysis calculates savings and performance for all measures relative to a base case. This base is the current Florida building code for new structures, and a typical residential building for existing South Florida homes. All measures were then ranked in terms of their technical potential to reduce energy use. Since interactions between many measures is pronounced, an incremental analysis was also performed to establish the measure specific ranking of the various options. Consideration of costs in the optimization process helps to guide selection of the most cost effective combinations of measures.
2. Residential Energy Use in South Florida
Residential buildings account for roughly half of Florida's electrical energy use and are responsible for approximately $5 billion in annual energy expenditures. As outlined in the current demand side management study (DSM) for the state, FPL's South Florida region accounts for some 23,450 GWh in residential electrical sales (SRC, 1992). This represents greater than one third of all residential electrical energy use in the state. Some 48% of these customers in the area live in single-family homes. The average single-family household in South Florida uses about 15,000 kWh annually.
Figure 2 and Table 1 shows the estimated electrical end-uses in a typical Miami home. Also given is the appliance saturation, or percentage of homes possessing various types of electricity using equipment. The energy end uses reflect the hot and humid climate. An estimated 38% of electrical energy is used for air conditioning; space heating is a relatively minor fraction. Refrigeration and water heating both comprise 14% and 12% respectively. The remainder includes lighting, cooking, clothes washing and drying, dish washing and swimming pool pumps. Several appliances are particularly energy-intensive: central air conditioners were estimated to use an average of 5,710 kWh per year, swimming pool pumps use 3,120 kWh, water heaters use 2,130 kWh and freezers and refrigerators use 1,830 and 1,770 kWh respectively.

Typical
End-uses |
Annual
kWh |
Appliances Saturation (%) |
| Central Air Conditioner | 5708 |
78.7 |
| Water Heating | 2134 |
83.3 |
| Frost-free Refrigerator | 1766 |
98.0 |
| Lighting | 1000 |
100.0 |
| Clothes Dryer | 827 |
75.9 |
| Resistance Heating | 644 |
78.0 |
| Range/Oven | 627 |
86.1 |
| Dishwasher | 425* |
66.7 |
| Clothes Washer | 112 |
92.0 |
| Micellaneous | 1669 |
100.0 |
| Total | 14,912 |
---- |
Non-Typical End-uses |
||
| Swimming Pool Pump | 3,117 |
23.6 |
| Heat Pump | 1,309 |
3.9 |
| Room AC | 1,839 |
60.6 |
| Man. Refrigerator | 902 |
8.2 |
| Auto Defrost Freezer | 1,830 |
11.0 |
| Manual Defrost Freezer | 1,321 |
8.2 |
| Source: SRC Energy conservation and Energy Efficiency in Florida: The Second Decade, Phase I Final Report, Synergic Resources Corp., p. C-40, July, 1992. | ||
| * Total for dishwasher energy use includes hot
water use associated with machine operation. Dishwasher energy use itself is < 200 kWh/yr. |
||
The energy demand of Florida homes has important consequences. Each home using the average amount of electricity requires approximately 6 tons of coal, or 160,000 cubic feet of natural gas to produce its annual electricity -- a fact that is becoming more important in Florida as the state is forced to rely more on fossil fuels for meeting its future electrical needs. The combustion of the coal or natural gas will produce between 10 and 18 tons of CO2 annually. Carbon dioxide is the major greenhouse gas which climatologists believe may lead to global warming. This effluent is also not the only concern: for each 15,000 kWh of electricity produced by coal combustion, some 200 pounds of sulfur dioxide are released into the atmosphere -- a major ingredient in the formation of acid rain.
Increases in electrical demand from Florida households leads directly to the need for additional power plants and distribution facilities. Each home added to the utility system an increase in diversified coincident peak demand of approximately 4 kW (Davis and Adams, 1988). Thus, under current efficiencies, each additional 50,000 single family homes will require a 200 MW combined cycle power plant to service them. Of the summer peak demand, over half (2.8 kW) is from central air conditioning systems (FPL, 1988).
Finally, the energy use of South Florida homes has economic implications. At current prices, the average household will spend over $1,200 per year to pay for its electricity use. Given the nearly one million residential customers in single family homes in South Florida, this cost accounts for an energy-related expense of over $1 billion annually to the local economy. These costs are further increased if those living in multi-family or manufactured homes are included in the total.
3. Building Energy Efficiency
A number of means exist with which to reduce energy use in buildings. Since cooling loads comprise the largest portion of overall savings energy use in Florida homes, measures to reduce its magnitude have the greatest overall potential. We first consider an analysis where base existing and new residential buildings are defined. All potential measures are then indexed against these base buildings in order to determine measure-specific savings. However, because of interactions among measures, such individual savings are not additive. This analysis is performed through the use of a detailed building energy simulation.
Improvement Priorities
Many of the surviving buildings in the affected area sustained extensive damage. The nature of the damage provides a convenient guide for setting priorities for improvements to South Florida buildings. The vegetative landscape of the region was devastated by the storm. Estimates show that up to 65% of the landscape cover in South Dade was destroyed (Schillaci and Moran, 1992). The 30-mile swath of the maximum storm winds saw the landscape almost totally denuded. The massive loss of trees and shrubs have potentially detrimental impacts on building energy use. Vegetation provides beneficial shading of individual buildings and community level reductions in ambient temperature from shading and evapo-transpiration (Akbari et al., 1992).
Physically, many buildings lost portions of their roofs. With typical construction, the roof portion of the average South Florida home is typically the greatest source of summer heat gain to the structure. Roofing choice, therefore has significant implications for overall energy efficiency. Many homes also lost windows. Window attributes are important in sub-tropical climates since they potentially represent the largest area-normalized cooling loads in residential buildings.
Homes to be totally re-built in the South Florida area offer a potentially greater opportunity for energy efficiency than existing structures. Both frame and block houses can be well insulated and supplied with superior equipment and appliances. Enforcement of the building energy code can provide assurance that the first step in achieving energy efficiency is taken.
Caveats
It is important to note the limitations of this preliminary study. The analysis has been confined to new and existing single family homes. Although, many of the options described here would likely be applicable to multi-family and manufactured homes, no effort has been made to include them in the analysis.

Figure 3: The variety of roofing damaged caused by Andrew
in the Kendall area.
The greatest attention has been paid to performing a sound analysis of the potential savings of the various measures considered. However, actual realized savings will vary in individual cases. Differences in floor area, thermostat schedules, appliance energy use, schedules and ventilation operation can easily vary end-use energy consumption from the average estimates for individual homes by more than 2:1 (Parker, 1990; Lutz, 1992). Also, some measures, such as the shading of air conditioner condensers, do not have well substantiated savings and are impossible to simulate with the current generation software. As a conservatism in such cases, we selected the low end of the savings potential, believing it better to err on the side of savings underestimation.
The most difficult numbers to establish in the study have related to the various measure costs. We attempted to gather several sources on each and to take the mean of the resulting values. This, of course, is subject to the hazards of taking averages on a small sample. Many measures to be considered are not typical practice and therefore have possibly greater current costs than would be reasonably expected with greater market demand and competition.
Although this study recognizes the large potential electricity savings associated with substitution of natural gas for heating, water heating, clothes drying and cooking end-uses, this question has been purposely ignored. Peak load impacts for such substitution can be large, particularly for space heating and cooking end-uses (Shlachtman and Parker, 1981). A more extensive future analysis might do well to consider fuel substitution. However, this should be conducted with an eye to the overall capacity of the existing natural gas pipeline infrastructure and the relative cost/benefit of such measures.
4. Building Simulation Analysis
A detailed hourly building energy simulation, DOE 2.1D, was used to assess methods of reducing the building sensible and latent cooling loads to a practical minimum. DOE 2.1D is a state-of-the-art fourth-generation building energy simulation program that has been developed by the Building Simulation Group at the Lawrence Berkeley Laboratory (LBL, 1984). The program, whose development was sponsored by the U.S. Department of Energy, is a well-documented public domain computer program for analyzing building energy use. DOE-2 predicts the hourly energy use and energy cost of building given hourly weather data, a detailed description of the building, its HVAC equipment and the prevailing utility rate structure. The program is particularly suited to the analysis since over 200 annual simulations were necessary for the analysis. Other simulation models, although some are more detailed, can require several hours of CPU time for a single run. DOE 2.1 performs an annual simulation on a two-zone residential building in about thirty seconds on a VAX 4500.
The simulations were performed on an hourly time step with results compiled, both on an annual basis (8,760 hours) and for the peak summer and winter days. Typical Meteorological Year data (TMY) for Miami, Florida was used for the analysis. The peak summer day was defined as the day in Miami on the TMY tape with the highest cooling loads; the peak winter day was the date with the lowest temperature. These two were August 4th and December 16th, respectively. Current FPL residential utility rates were used for the economic analysis. These rates average $0.08 kWh including fuel-charges and other expenses.
Building Prototypes
A prototype building, representative of residential structures in southern climates, was used for the analysis. The building has a 1,500 ft2 design which is described in detail elsewhere (Fairey et al., 1986). Figure 5 illustrates the building floor plan. Table 2 summarizes the fundamental specifications used for our simulations. The prototypes were created to allow assessment of improvements, both to new building construction, as well as to existing structures:

Table 2
Building System Specifications for Base Case Building
| Primary Characteristics | |
| Type: | Single-story, rectangular floor plan |
| Orientation: | Long-axis faces north-south |
| Floor Area: | 1,500 ft²; slab-on-grade |
| Roof: | Asphalt shingles on plywood decking; 22.6º roof slope |
| Overhang: | 2 foot around entire perimeter |
| Ceiling Insulation: | New: R-19 over 1/2" sheetrock Existing: R-11 over 1/2" sheetrock |
| Wall Construction: | New: Frame, R-11 insulation Existing: concrete block, no insulation |
| Wall Absorptance: | 0.6, medium-tan color |
| Roof Absorptance: | 0.8, gray asphalt shingles |
| Windows: | 224 ft²; single glazed with aluminum frame with curtains and some site shading, base shading coefficient = 0.60 |
| Heating and Cooling | |
| Heating: | Resistance strip heat, 30,000 Btu/hr |
| Cooling: | 3-ton AC, SEER = 10.0; SHR = 0.75 |
| Distribution | Attic-mounted duct system; R-4.2 rigid-board fiberglass insulation |
| Appliances | |
| Electric Water Heater: | Storage type, 40 gallon size, 2,134 kWh/yr |
| Existing Refrigerator: | 1,766 kWh per year |
| New Refrigerator: | 1,000 kWh per year |
| Lighting: | Incandescent; 1,000 kWh/yr |
| Clothes Dryer: | 827 kWh |
| Range: | 627 kWh |
| Dishwashers: | 425 kWh |
| Operation | |
| Heating Thermostat: | 70ºF |
| Heating Setback: | 68ºF (8 AM - 5 PM; 12 - 7 AM) |
| Cooling Thermostat: | 78ºF |
| Cooling Setup: | 80ºF (8 AM - 5 PM) |
| Internal Heat Gains: | Averages 648 W |
| Cooling Season: | March - October |
Schedules
We assume three occupants in the prototype home with typical electrical appliances and associated energy use. The specific end-use electrical demand profiles were taken from sub-metered appliance load data gathered from a large sample of homes during the summer months (Pratt et al., 1989). These aggregate profiles were then used to create a schedule for internal heat gains in the building. All simulation inputs were checked against established EPRI guidelines for engineering methods used for such analysis (AEC, 1992).
The thermostat schedule was based on a study by a Florida utility which monitored thermostat settings of a number of residential buildings (Gulf Power Co., 1987). The "base case" building was intended to be representative of conventional residential building practice in the Florida area. From this "reference" building, simulations were performed parametrically to examine the individual effects of each energy efficiency measure (EEM) considered. This allowed identification of the most promising options.
5. Energy-Efficiency Measures
Table 3 summarizes the various EEMs considered in our initial analysis.
Table 3
Listing of the Studied Measures
Measure Title |
Description |
| 1. Base 2. Adv. Heat Pump 3. Hi-Eff. Heat Pump 4. H. Eff. AC 5. Zoned Building 6. Programmable Thermostat 7. Duct System Interior 8. Seal Duct System 9. Radiant Barrier 10. Reflective Roof 11. R-30 Attic Insulation 12.Landscaping (mature) 13. Landscaping (new) 14. Shade AC Condenser 15. Dbl-Pane Low-E, SS 16. Dbl-Pane Low-E, Refl. 17. Dbl-Pane windows 18. Single Pane, Lam/Low-E 19. Single Pane, Reflective 20. Single Pane, SS 21. Single Pane w/ Window Film 22. Single Pane, Refl. E/W 23. Window Awnings 24. R-19 Walls 25. Insulated Door 26. White Walls 27. Whole House Fan 28. Ceiling Fans 29. Infiltration Control 30. Reduce Appliance Gains |
Base Building Advanced heat pump (SEER=15.5; HSPF=10.0) High Eff. H. Pump (SEER=12; HSPF=8.0) High Eff. Air Conditioner (SEER=12.0) 50% of building conditioned: 2 AC systems Programmable thermostat installed Duct system located within conditioned space 70% of duct leakage sealed Attic radiant barrier installed Reflective roof coating applied Attic insulation increased from R-19 to R-30 Mature tree canopy shades 67% of walls/windows Newly installed landscape shades 25% of walls Landscape shading of AC condenser Double pane, low-E spectrally selective windows Double pane, low-E reflective Double pane, aluminum frame, 3/8" air space Single pane, laminated, low-e with selective coating Single pane, reflective coating Single pane, selective surface Reflective window film applied to windows As above but only on east and west windows Fabric or metal window awnings installed Wall insulation increased to R-19 R-5 metal door installed White colored walls Add 36" whole house fan to increase ventilation potential Add 6 ceiling fans to increase ventilation potential Weather stripping and caulking High Eff. Refrigerator and lighting cuts gains |
6. Simulation Results
New Frame Construction
The simulations were completed on an annual basis with each parametric run being compared with the base case. Results are summarized in Table 4 ranked by the measures providing the greatest overall electrical consumption savings relative to the reference configuration:
Table 4
Parametric Simulation Results for New Frame Construction
| Measure Description |
Heating kWh |
Cooling kWh |
Total kWh |
Difference kWh |
Heating Peak kWh |
Cooling Peak kWh |
| Reference Case | 555 |
4788 |
5344 |
0 |
4.03 |
2.43 |
| Advanced Heat Pump | 362 |
3177 |
3538 |
1806 |
1.76 |
1.61 |
| Zoned Building | 365 |
3661 |
4027 |
1317 |
2.51 |
1.70 |
| Dbl. Pane, Low-E, SS | 370 |
3811 |
4181 |
1163 |
2.86 |
2.00 |
| Landscaping (mature) | 702 |
3549 |
4251 |
1092 |
4.11 |
2.01 |
| Dbl. Pane Low-E, Refl. | 418 |
3901 |
4319 |
1025 |
3.12 |
2.04 |
| Duct System Interior | 476 |
3960 |
4436 |
908 |
3.45 |
2.01 |
| Single Pane, Lam. Low-E | 571 |
3873 |
4444 |
900 |
3.75 |
2.09 |
| High Eff. Heat Pump | 392 |
4085 |
4477 |
867 |
1.91 |
2.08 |
| Single Pane, Refl. | 643 |
3970 |
4613 |
731 |
4.08 |
2.15 |
| Hi. Eff. Air Conditioner | 555 |
4087 |
4642 |
701 |
4.03 |
2.08 |
| Sealed Duct System | 511 |
4190 |
4701 |
643 |
3.70 |
2.13 |
| Window Awnings | 628 |
4094 |
4722 |
622 |
4.07 |
2.20 |
| Single Pane, SS | 621 |
4160 |
4780 |
563 |
4.07 |
2.22 |
| Refl. Dbl.: E/W Windows | 519 |
4378 |
4898 |
446 |
3.75 |
2.21 |
| Reflective Roof | 579 |
4335 |
4914 |
430 |
4.04 |
2.21 |
| Landscaping (new) | 597 |
4334 |
4931 |
413 |
4.05 |
2.27 |
| Radiant Barrier | 555 |
4389 |
4944 |
400 |
4.04 |
2.23 |
| Whole House Fan | 555 |
4400 |
4956 |
388 |
4.03 |
2.43 |
| Ceiling Fans | 541 |
4422 |
4963 |
381 |
3.99 |
2.25 |
| Dbl. Pane Windows | 397 |
4593 |
4989 |
355 |
3.24 |
2.30 |
| Single Pane, Refl.: E/W | 587 |
4405 |
4992 |
352 |
4.04 |
2.26 |
| Reduce Appl. Gains | 660 |
4376 |
5037 |
307 |
4.19 |
2.33 |
| R30 Attic Insulation | 468 |
4648 |
5116 |
228 |
3.71 |
2.31 |
| Programmable Thermostat | 511 |
4607 |
5118 |
226 |
4.03 |
2.54 |
| Shade AC Condenser | 555 |
4675 |
5231 |
113 |
4.03 |
2.37 |
| R19 Walls | 474 |
4762 |
5236 |
108 |
3.69 |
2.39 |
| Infiltration Control | 532 |
4721 |
5253 |
91 |
3.89 |
2.38 |
| White Walls | 560 |
4701 |
5261 |
82 |
4.03 |
2.41 |
| Insulated Door | 538 |
4778 |
5315 |
28 |
3.96 |
2.43 |
The simulation analysis results for new South Florida homes showed that all proposed measures would provide some level of energy savings. However, the individual improvements showed varying degrees of effectiveness. The more productive individual measures included high efficiency heat pumps or air conditioners, high performance windows, the shading from mature landscaping and the location of the duct system within the conditioned space of the building. All these options provided stand-alone reductions in annual heating and cooling energy use of 20% or more.
Concrete Block Construction
Recognizing that block construction is a large fraction of new residential buildings in South Florida, we also created a CBS residential prototype. The energy code in Florida requires only a minimum R-3 insulation (1-inch of fiberglass) be installed on the concrete block wall interior. We analyzed measures which we believed would have significant interactions with concrete walls. This included increased insulation, both interior and exterior, changes to wall color and landscape shading. The results are given in Table 5. They show that CBS construction under code levels of thermal integrity are generally equivalent to R-11 frame walls. They also indicate that increases to concrete block wall insulation level on the interior do not significantly improve performance in Miami. However, increased insulation on the exterior of the concrete block walls, does provide reductions in both heating and cooling energy use. We did find that landscape shading of walls was a more important improvement for concrete block than for frame construction. This is due to the lower insulation level.
Table 5
Simulation Results for New CBS Construction
| Measure Description |
Heating kWh |
Cooling kWh |
Total kWh |
Difference kWh |
Heating Peak kWh |
Cooling Peak kWh |
| 1. Frame Case | 555 |
4788 |
5344 |
72 |
2.43 |
4.03 |
| 2. Block Reference Case* | 592 |
4680 |
5272 |
0 |
2.39 |
4.33 |
| 3. Block/R-11 int | 476 |
4733 |
5209 |
-63 |
2.37 |
3.77 |
| 4. Block/R-11 ext | 337 |
4464 |
4801 |
-471 |
2.24 |
3.21 |
| 5. Block/White Walls | 627 |
4530 |
5157 |
-115 |
2.34 |
4.36 |
| 6. Block/Landscaping (new) | 658 |
4209 |
4867 |
-405 |
2.23 |
4.37 |
| 7. Block/Landscaping (mature) | 823 |
3404 |
4227 |
-1045 |
1.97 |
4.45 |
* Light-weight 8" concrete
blocks with R-3 fiberglass insulation on the interior. |
||||||
Analysis of Architectural Influences on Energy
Several parametric runs were performed to the determine the influence of common architectural options. These included the impact of non-optimal building orientation (long axis of the building faces east/west), the benefits of overhangs (the standard building has 2 foot overhangs around the entire perimeter), the energy liability of a 2 x 4 foot south facing single-glazed skylight and the added infiltration from a poorly sealed fireplace (no damper). In the later case, the average infiltration rate (0.4 ACH) was increased by 10%.
Table 6
Simulation Results for Analysis of Architectural Features
| Measure Description |
Heating kWh |
Cooling kWh |
Total kWh |
Difference kWh |
Heating Peak kWh |
Cooling Peak kWh |
| 1. Reference Case | 555 |
4788 |
5344 |
0 |
2.43 |
4.03 |
| 2. East/West Orientation | 555 |
4933 |
5489 |
145 |
2.55 |
4.04 |
| 3. No Overhangs | 555 |
4879 |
5434 |
90 |
2.47 |
4.04 |
| 4. Skylight | 560 |
5013 |
5573 |
230 |
2.52 |
4.08 |
| 5. Fireplace | 574 |
4842 |
5416 |
72 |
2.48 |
4.13 |
| 6. No Natural Ventilation | 555 |
6498 |
7053 |
1709 |
2.43 |
4.03 |
The results verify traditional architectural wisdom. Adequate cross-ventilation to avoid air conditioning during milder weather conditions can make a large difference (32%) in annual space cooling energy use. A north-south orientation reduces space energy use by about 3% relative to an east-west facing. A standard 2 foot overhang reduces energy consumption by about 2%. Skylights and fireplaces are efficiency liabilities.
Existing Homes
Table 7 presents the analysis results for the various measures analyzed for existing South Florida houses. The base case is a typical CBS structure with uninsulated walls and R-11 insulation in the attic. The last two parametric runs in the table examine the increased use associated with no attic insulation and a reflective roof substituted on such buildings that cannot be insulated.
Table 7
Simulation Results for Existing Construction
| Measure Description |
Heating kWh |
Cooling kWh |
Total kWh |
Difference kWh |
Heating Peak kWh |
Cooling Peak kWh |
| Reference Case | 1043 |
6033 |
7076 |
0 |
5.92 |
3.73 |
| Super Eff. Heat Pump | 740 |
3133 |
3873 |
3203 |
3.01 |
1.70 |
| High Eff. Heat Pump | 740 |
4035 |
4775 |
2301 |
3.01 |
2.21 |
| High Eff. A/C | 1043 |
4040 |
5083 |
1993 |
5.29 |
2.21 |
| Mature Landscape | 1443 |
4214 |
5657 |
1418 |
6.29 |
3.09 |
| Awnings | 1279 |
4852 |
6131 |
944 |
6.21 |
3.29 |
| Sealed Duct System | 959 |
5353 |
6312 |
764 |
5.44 |
3.09 |
| Ceiling Fans | 1025 |
5298 |
6323 |
753 |
5.90 |
3.28 |
| Reflective Roof | 1086 |
5359 |
6446 |
630 |
5.94 |
3.40 |
| New Landscape | 1167 |
5358 |
6525 |
551 |
5.97 |
3.48 |
| Whole House Fan | 1043 |
5503 |
6546 |
530 |
5.92 |
3.73 |
| Window Film: E/W | 1062 |
5565 |
6627 |
449 |
5.79 |
3.48 |
| R-30 Attic | 902 |
5757 |
6659 |
417 |
5.46 |
3.52 |
| White Walls | 1130 |
5585 |
6715 |
361 |
5.96 |
3.56 |
| Reduce Appl. Gains | 1180 |
5551 |
6713 |
345 |
6.07 |
3.61 |
| Programmable T-stat | 967 |
5787 |
6755 |
321 |
5.92 |
3.84 |
| R-19 Attic | 971 |
5888 |
6858 |
217 |
5.68 |
3.63 |
| Shade A/C Condenser | 1043 |
5890 |
6933 |
142 |
5.92 |
3.63 |
| Infil. Control | 1022 |
5958 |
6980 |
96 |
5.81 |
3.67 |
| No Attic Insulation | 1482 |
6908 |
8390 |
-1314 |
7.35 |
4.23 |
| No Attic/Refl. Roof | 1602 |
5407 |
7009 |
69 |
7.37 |
3.53 |
The simulation results for existing homes show the large potential benefits available for replacing existing lower efficiency air conditioners with newer high-efficiency models. Also, the lack of wall insulation makes white walls or landscape shading relatively more desirable than with new homes. Application of reflective window films was only analyzed for the east and west building faces in interest of preserving interior daylight and for addressing aesthetic concerns.
7. Detailed Description of the Measures
A variety of proven technologies are available to reduce building energy use. Below, we detail the various analyzed measures. Pertinent FSEC research on many of the described technologies is summarized in Appendix A.
Thermal Distribution System
Most South Florida residences feature central air conditioning with an air distribution system located in the attic space. Previous analysis using a very detailed finite element simulation, FSEC 3.0, has shown that Florida residences with such thermal distribution systems potentially use up to 30% more space cooling energy than would a system with sealed duct work within the unconditioned space (Parker, Fairey and Gu, 1992). These losses include both forced air leakage and heat transfer to the attic mounted duct system. Use of the simulation showed that duct heat transfer increased cooling energy use by approximately 8%. Duct air leakage can lead to highly variable increases in cooling and heating energy use. With a typical area of audited duct leakage, loads were predicted to increase by about 14% relative to a system with 70% of the leakage sealed. The combined effect serves to reduce effective air conditioning cooling efficiency by approximately 21%. Examination of the effects under heating conditions showed a similar magnitude of losses. The 21% reduction in efficiency is conservative since measured results from sealing about 70% of discovered duct leakage alone, saw measured reductions in cooling energy use of 17.2% (Cummings et al., 1991). Other studies of the impact of duct losses on overall HVAC efficiency have concluded even greater impacts. Modera et.al., (1992), Koomey (1991) and Andrews (1992) have all cited average reductions to efficiency of 30% or more.
Unfortunately, DOE 2.1D, as currently configured, has no method of comprehensively incorporating duct system heat gains or air leakage to the thermal distribution system (Huang, 1991). This was accommodated in our simulations by adjustment to the seasonal efficiency of the heating and cooling equipment. The exact multipliers used in our analysis for heating and cooling efficiency were based on annual simulation results using FSEC 3.0 and are detailed in Appendix B.
Orientation and Architecture
The energy savings potential of proper building orientation has been long recognized (Olgyay, 1965). Shading from fixed devices, such as overhangs, are also effective in South Florida (Buffington, Sastry and Black, 1981; McCluney, 1983). As part of our parametric analysis, we examined these influences. This was done by changing the prototype building's orientation from the long axis facing north and south (the optimal orientation) to east and west. The savings of fixed shading was examined by deleting the continuous 2-foot overhangs in the building. Typical of current practice, the windows were assumed to be located at a height of 6.75 feet from grade level.
Natural Ventilation
Natural ventilation of residential buildings is an effective and well understood traditional cooling method (Fairey, Chandra and Kerestecioglu, 1986). The base case analysis assumes that South Florida residences are mechanically air conditioned from March 1st through November 30th. This is accomplished by a thermostat setting of 90oF for the non-cooling months. The assumption is that natural ventilation will provide most of the necessary cooling during the three Miami "winter months." Similarly, heating is assumed from December 1st through February 28th. The resulting month-by-month predicted heating and cooling energy use is shown for the new frame base in building Figure 6. We ran a single case where air conditioning was assumed to be used year round. The results of this case allowed a determination of the specific benefit of natural ventilation for reducing air conditioning use. This case, shown in Table 5, indicates that the availability of natural ventilation reduces cooling energy use by 32%, or 1,709 kWh per year over year-round closed building operation.

Whole House Fan
Whole house fans exhaust large quantities of air from the house interior to the attic space. This provides forced ventilation even when local wind velocities are low. Typically fans are operated during the cooler evening hours to take advantage of ventilation rather than air conditioning. Such a strategy provides a longer "ventilation season" in Florida since nighttime windspeeds are typically lowest during the summer months. A recent study in Central Florida found that whole house fans dropped the average nighttime interior temperature by 2 - 6oF when operated during summer conditions (Parker, 1991). This is potentially important since a statistical survey analysis of 384 homes in Central Florida found that each month that a household claimed to use natural ventilation rather than air conditioning averaged annual electricity savings of 388 kWh (Vieira and Parker, 1991).
The implication is that electricity can be saved if the natural ventilation season can be extended and vapor-compression air conditioning is reserved for only the hottest periods. A detailed computer analysis of potential savings from whole-house fans by Kusuda and Bean (1981) for Houston, Texas found a 24% air conditioning savings potential. Burch and Treado (1979) measured the savings of a whole-house fan on air conditioning in a house in Houston. The fan was operated when the temperature outside was less than 82oF and greater than 75oF. They found the air conditioning energy use reduction were well correlated with the daily average outdoor temperature. Savings varied from 65% at 76oF to 10% at 84oF. Of greatest pertinence, however, is a field study of a home in Gainesville, Florida which found a 22% air conditioning savings using a similar control strategy with a whole house fan in the summer of 1982 (Ingley et al., 1983).
Our study made simple and conservative assumptions relative to the potential savings of whole house fans, checking reasonableness of our results against the above field studies. We assumed that whole house ventilation could obviate the need for air conditioning in the months of February - April and October and November in Miami. Based on an electric demand of 300 Watts and 12 hour operation, we assumed 3.6 kWh per day is used by fan operation. The differential between the predicted air conditioning energy consumption for these months and the average 110 kWh for whole house operation comprised realized savings. As expected, savings were greatest for the months of October and April, but were still less than 200 kWh per month.
One consideration which can serve to greatly reduce the effectiveness of this strategy is consideration of humidity levels. Restriction of outdoor air ventilation to periods when the air temperature is between 82o and 75oF exacts one limitation. However, limitation to periods when relative humidity is less than 70% will greatly reduce its effectiveness. We assumed that this was not a limitation, although it does create a bias against general application of this option.
Ceiling Fans
The ability of ceiling fans to improve human comfort during the cooling season is well understood (Fairey, Chandra and Kerestecioglu, 1986). We examined the added cost of installing six quality ceiling fans ($600) and assumed this would allow the cooling thermostat setting to be elevated by 2oF when occupants were home. This increased the cooling thermostat setting to 80oF. The house was assumed to be occupied between 5 PM and 8 AM on weekdays and all day on weekends. The analysis is based on the fans running an average of eight hours per day on medium speed, drawing 30 watts each. This electricity consumption (44 kWh/month) was added to the DOE 2.1D estimated cooling energy use. The building's internal heat gains were also increased by 205 Btu/hour to account for the additional heat released from operation of the fans.
Simulation results showed an 8% reduction in space cooling energy use for new homes even after the direct energy use of the ceiling fans and internally released heat was taken into account. Savings were over 12% for existing homes. However, it must be pointed out, that the realized savings of this measure is exceedingly sensitive to thermostat behavior in response to fan use (see Figure 4 and associated discussion).
Heating and Cooling Equipment
The relative efficiency of heating and cooling equipment in residences has a direct impact on building energy use. The long cooling season in Miami suggests the importance of air conditioning equipment efficiency and capacity. Several field studies exist showing excellent savings from the substitution of high efficiency air conditioning equipment in replacement of existing less efficient units (Parker, 1990; Burns and Hough, 1991; Ternes and Levins, 1992). Measured savings were on the order of 20 - 40% of pre-retrofit cooling consumption.
We assume that the Seasonal Energy Efficiency Ratio (SEER) of existing Miami residential air conditioning equipment averages 8.0 Btu/W. The equipment has an average 36,000 Btu/hr (3-tons) capacity with a sensible heat ratio of 0.75. Typical new air conditioning equipment is assumed to consist of a three-ton SEER 10.0 air conditioner. Both new and existing buildings are assumed to have strip heat (forced air resistance heating systems).
High efficiency air conditioners are assumed to be SEER 12.0 with an incremental cost over standard units (SEER 10) of approximately $400 (Cummings, 1988). Similarly, the high-efficiency heat pump has an SEER of 12.0 with a Heating Season Performance Factor (HSPF) of 8.0 Btu/W. This option has an incremental cost of $1,200 relative to a straight SEER 10.0 air conditioning system.
An advanced heat pump is also analyzed, representing the most efficient air-to-air equipment currently available. It is based on an variable-speed Carrier unit with an SEER of 15.5 and a HSPF of 10.0.
This configuration has an incremental cost of approximately $2,500 relative to a straight three-ton SEER 10.0 air conditioner. The validity of the above cost data was established through a series of contacts with local air conditioning and heating contractors (see Appendix C).
Our analysis indicated this to be one of the most effective efficiency improvement options. The advanced heat pump demonstrated the potential of reducing energy use by 33% in new construction and by 45% in existing buildings. Both heating and cooling peak loads were also substantially reduced. Note, however, that the DOE 2.1 predicted reductions to peak cooling loads are likely misleading for variable-speed air conditioning units since they may have higher demand under full load than conventional single-speed high-efficiency units (Henderson, 1990).
Programmable Thermostat
One potential measure is a fully programmable thermostat to control the heating and cooling system. These thermostats allow seven-day scheduling of temperature control including holidays. The primary advantage is that of reliably setting back or up the thermostat when the building is unoccupied. We conservatively assume that the impact of the programmable thermostat will be to increase the depth of the setback or setup by 1oF. The justification is that the increased setback/setup will be realized due to the improved reliability with which the changed settings are made. The normal heating season setback is 68oF from 11 PM to 7 AM and from 9 AM to 5 PM during weekdays. The normal cooling season setup is 80oF from 9 AM to 5 PM during weekdays. There is no setback or setup during daytime hours on weekends or holidays. Programmable thermostats cost between $70 and $150. We assume the measure costs $200 including installation.
Simulation results showed that the option reduced heating and cooling energy use by about 4% for new buildings, although actual savings would be very sensitive to the degree of setback or setup achieved in individual cases. We also, note that this strategy has the potential of aggravating peak loads, since the heating or cooling system is often activated during periods coincident with utility system peak loads.
Zoning
Air conditioning contractors have long known that zoning the sections of a home so that only part of the space is conditioned can save electricity. Analysis of potential energy savings from zoning was accomplished as follows: The 30 x 50 foot rectangular living space in the prototype was sectioned into two separate 30 x 25 foot zones separated by an uninsulated partition wall and a closed door. One section of the home was then conditioned for the evening hours from 11 PM to 7 AM; the other section was conditioned for the remainder of each day.
The thermostat schedule was apportioned and internal heat gains were split between the two spaces. Rather than a single 3-ton air conditioner; we assumed that a separate two-ton AC was used for each space along with required duct work and separate thermostatic controls. The cost premium for the two air conditioners and added detail for the distribution system and thermostats was determined to have an incremental cost of $1,200.
As expected, analysis showed this to be a very effective strategy to reduce heating and cooling energy use. However, we did not include it in the incremental savings analysis or in the overall economic assessment. This was not done because the measure involves a reduction in amenity for the household, and we desired that our final analysis be life-style neutral for its prime recommendations. For those who do not find such partitioning objectionable, the strategy can provide considerable savings. Estimates indicated a 25% reduction in combined heating and cooling energy use.
Window Options and Shading
A variety of window types were simulated for the new building prototype. A much more detailed description of the different products and their characteristics is contained in Appendix D and a simultaneously issued FSEC research report (McCluney and Gueymard, 1992). Table 8 summarizes the input data used for the simulated glazings. All windows were assumed to be installed in thermally-broken aluminum frames. The U-values for various glazings were modified according to the frame types in Table 13 of Chapter 27 of the Handbook of Fundamentals (ASHRAE, 1989). Double-pane windows were assumed to be separated by a 3/8" air space.
For existing buildings, the analysis was confined to the base case (single pane, clear) and single pane with reflective window film added as the retrofit measure. Based on a previous analysis (Parker, 1989) we examined window treatments to east and west windows as a competing measure with uniform changes to all windows. The greater solar exposure of these building faces provide superior thermal and economic performance. This was also based on a desire to address concern for aesthetics (the most effective films are reflective) and to prevent daylight levels on the interior from being excessively reduced. "Dark windows" which reduce interior levels of illumination and lead to increased use of artificial lighting can nullify any potential thermal savings.
Table 8
Simulated Window Characteristics
Code |
Description |
Shading Coefficient |
U-Value (Btu/hft²ºF) |
Visible Transmittance |
Incremental $ Cost/ft²* |
| SP | Single-pane glass, clear | 1.00 |
1.10 |
90% |
$0.00 |
| SPR | Single-pane, reflective coating | 0.51 |
1.10 |
27% |
$2.00 |
| SPWF | Single-pane/reflective window film | 0.42 |
0.79 |
50% |
$3.00 |
| SPSS | Single-pane with selective surface (blue) | 0.62 |
1.10 |
72% |
$4.30 |
| SPLAM | Single-pane/laminated with low-e film | 0.39 |
0.87 |
54% |
$10.00 |
| DP | Double-pane, 3/8" airspace | 0.81 |
0.60 |
82% |
$2.50 |
| DPLESS | As above with selective surface | 0.33 |
0.37 |
56% |
$10.00 |
| DPR | Double-pane with reflective film | 0.42 |
0.60 |
26% |
$6.00 |
* Includes frame and installation. |
|||||
Our analysis assumed that pre-existing window shading was present in the form of curtains, blinds, landscaping and shadowing from adjacent buildings. All these factors were estimated to change the base case shading coefficient from single-pane clear glass from 1.0 to 0.6. This more realistic assumption tends to reduce the magnitude of the savings realized from window shading and glazing changes. The characteristics for individual glazing systems were then used to modify the shading coefficient input into the model. Similarly, we used the Handbook of Fundamentals to determine an average shading coefficient for awnings. Cost data was collected from vendors of the various glazing types and shading devices. As expected, many of the higher performance glazing types have premium prices.
Analysis results showed high performance windows to be among the most promising measures in terms of energy savings for new buildings. "Superwindows" with low-e coating, a selective surface and a high visible transmittance demonstrated the potential of reducing space conditioning loads by up to 22% in new residential buildings. As expected, savings were disproportionately greater for adding high performance windows to the east and west faces of the analyzed buildings.
Landscaping
With sustained winds exceeding 140 mph, Hurricane Andrew destroyed or damaged the majority of the trees in South Dade County. Re-establishing the landscape can help to save energy. The energy savings potential for landscaping in South Florida has been well established by experimental studies performed at Florida International University (Parker, 1983). Recognizing the changing potential of this measure over the building life, we estimated savings of both newly installed vegetation and of a mature landscape with fully grown tree canopies. In either case, the landscape planting is to be strategically placed to provide shade to the east, west, southeast, and southwest faces of the prototype building. We assumed that the newly installed landscape would shade 25% of the walls and windows in these directions; the mature landscape was assumed to provide 67% shading. As a conservatism, no credit was taken for possible temperature reductions due to evapo-transpiration. The shading is provided from the purchase of six 6 - 8 foot live oak trees. The installed purchase price of these specimens, with a six-month guarantee, was $740. Several nurseries provided similar price estimates.
A recent EPA study recommends shading of exterior air conditioning condensers, using landscaping or other means, as a method to reduce space cooling energy use (Akbari, et.al., 1992). Estimated theoretical savings of such a strategy have ranged from 1 - 10% (Parker, 1983; Abrams, 1986). Unfortunately, no empirical research has been conducted to measure the actual cooling energy savings that can be achieved with this strategy. Given the uncertainty, we chose a conservative estimate with the AC condenser shading conferring a 2% enhancement to the air conditioner seasonal efficiency. This assumes the air temperature being drawn into the condenser unit is dropped by about 2oF by the cooling influence of the landscaping. The benefits are provided by two 6 - 8 foot live oak trees which are located near the condenser unit if it is on the east or west faces of the home. Alternately, location of the condenser on the north face of the home could provide the shading benefits at virtually no cost.
Simulation results showed that a newly installed strategically planted landscape would be able to reduce cooling energy use by about 10%. A mature landscape with shading of the AC condenser could result in a reduction of up to 28%.
Attic/Ceiling Measures
Attic thermal performance is critical in cooling dominated climates since it affects heat gain across the ceiling surface. Control of attic temperatures is doubly important if air distribution ducts are located within this space, as is common in Florida home construction.
Radiant Barriers
A radiant barrier system (RBS) is a layer of low-emissivity foil material placed in an attic airspace to block radiant heat transfer between the hot roof and the top of the ceiling insulation. Extensive research at FSEC has proven that roof mounted RBS can reduce ceiling heat flux by 30 - 50% with annual cooling electricity savings of 7 - 12% (Fairey et al., 1986, 1988, 1989; Ober, 1991). Reductions to peak cooling loads are generally higher. Appendix A includes a comparison of the air conditioning load of two unoccupied frame houses in Gainesville, Florida which were monitored side-by-side with and without a radiant barrier. The RBS was found to save approximately 8% of cooling energy use. Mirroring such measurements, our simulation results predicted an 8% reduction in space cooling energy associated with the installation of a RBS.
A radiant barrier was estimated to cost $325 installed in the prototype building. Cost data were estimated through contacts with several vendors (see Appendix C). The range is in general agreement with the costs encountered in a recent residential retrofit program in Oklahoma (Ternes and Levins, 1992). We did not specifically analyze radiant barriers for existing buildings. However, this will be feasible in some South Florida residences with enough attic space, or those which lost their roofs and are having them replaced. The cost/benefit of this measure for existing homes should mirror that for new buildings.
Reflective Roofs
Recent research at FSEC has focused on the influence of roof materials on thermal performance. Six small roof models have been constructed to evaluate the resistance to heat gain of various types and colors of roofing (Chandra and Moalla, 1992). Initial findings are summarized in the paper in Appendix A. Test cases have included black asphalt shingles, a white asphalt shingle roof with a reflective elastomeric coating and a series of red tile configurations. Results show that roof sections with white reflective coatings exhibit superior thermal performance to conventional roofing systems. Similar experimentation has been performed at Oak Ridge National Laboratories (Anderson et al., 1991) which found that reflective coatings significantly reduce the heat flux through roofs and hence building cooling loads. Recent research conducted this summer at FSEC examined the impact of a reflective coating applied to a residence at mid-summer. Air conditioning was monitored for three weeks before and after the coating was applied. Weather normalized air conditioning savings were approximately 20% with a constant thermostat setting and no change in other conditions. Although the attic floor is insulated with six inches of blown fiberglass (~R19), infrared thermography showed significant changes in ceiling heat flux. A synopsis of this research is contained in Appendix E.
Our simulation analysis predicted a 9% reduction in space cooling energy for new buildings with a reflective roof. As expected, estimated savings increase with lower ceiling insulation levels. Existing CBS residences with R-11 attic insulation were predicted to save 11%.
Reflective roofs have other non-house specific advantages over competing roofing options since increasing the community-wide albedo of roofs should serve to reduce the neighborhood air temperature (Bretz et. al. 1992). EPA has recommended increasing the use of white surfaces in hot climates option to reduce the magnitude of the urban heat island (Akbari et al., 1992). Although currently more expensive than radiant barriers and with a shorter measure life, this "community cooling" advantage of reflective roofs is one that radiant barriers and increased attic insulation do not possess.
Our simulation analysis assumed a reflective roof coating could be applied such that the effective roof solar absorptance dropped from 0.80 with gray asphalt shingles to 0.25 with a white roof (DSET Laboratories, 1992). The cost of the roof coating depends on the circumstance of the installation. For new roofs, we base our cost ($600) on the cost of sprayed-on acrylic latex paint. This material can provide the same thermal benefits without the added cost of the elastomer which would not be needed for a new roof. For existing residences, we assume no cost on the premise that the coating is applied as the existing roof is nearing the end of its useful life which increases its longevity while providing the thermal benefits. Since, the coating will significantly increase the life of the existing roofing system, not all costs of the coating should be attributed to its energy savings capability.
Other factors affect the potential for this measure. Since this EEM is in its infancy, we expect that the cost of a reflective roof could come down significantly as products, such as reflective shingles, are introduced (Jones, 1992). We assume a useful life of the measure of only ten years, although many manufacturers claim a greater longevity. Potential problems with mold and mildew staining make this a reasonable conservatism. Obviously, the development of reflective shingles or the use of a white tiled roof or white sheet metal roof would be expected to greatly extend measure life.
The use of reflective roof coatings is particularly attractive for existing homes in South Florida in which the ceiling cannot be insulated. Some of these structures have flat roofs or configurations with little or no accessible attic space. Reflective coatings can offer greatly reduced air conditioning consumption in these homes which were analyzed separately as special case. Results showed a 28% reduction in space cooling energy in existing uninsulated CBS structures, although space heating budgets were somewhat increased.
Attic Insulation
Addition of attic insulation represents a commonly considered energy savings measure for residences. Code levels in new South Florida homes is R-19 which forms our base case. Existing homes are considered to already have R-11 over the ceiling. However, there are still a significant number of residences in Dade County which are uninsulated. Many of these cannot be feasibly retrofit due to physical limitations. These include flat roofed buildings built in the late 1950s and others where there is virtually no cavity between the roof and ceiling.
Ceiling insulation is a well documented method to reduce the rate of heat transfer from the roof to the interior of residential buildings. Field measurement of the retrofit of ceiling insulation from R-11 to R-30 in a test home in Tennessee showed a 16% drop in measured cooling energy use (Levins and Karnitz, 1987). Addition of a radiant barrier system (RBS) in these tests also showed a similar level of cooling energy savings to that of R-30 insulation. However, these measurements were made in a home in which the air distribution system was located in the crawlspace. Larger savings from the RBS would be expected where the ducts were located in the attic, as is common in Florida homes.
We analyzed the impact of increasing attic insulation in existing homes from none at all to R-19; from R-11 to R-19 and from R-11 to R-30. In new homes, we examined the impact of increasing the insulation level from R-19 to R-30. Predicted savings were modest at 4% of overall heating and cooling energy use. Insulation from R-11 to R-30 in existing residences showed a 6% savings.
The incremental costs of these insulation levels are based on collected cost data (Appendix C and Cummings, 1988). It was assumed that the cost of going from R-19 to R-30 was $210; the cost from R-11 to R-19 was $110. Addition of R-19 insulation to an uninsulated ceiling was based on the costs of blown-in fiberglass with an average cost of $200 for the application. The measure was assumed to have a useful life of thirty years.
Reductions to Internal Gains
Reductions to appliance electricity use in Florida homes can be expected to have significant interaction with cooling and heating energy use. The reduced electrical consumption lowers the level of internally generated heat within the structure. This serves to decrease space cooling demand, while increasing heating energy use. However, the effects are not offsetting since heating and cooling efficiencies are usually different. Also, the length of the cooling season is much longer in South Florida.
The internal gain schedule in the analysis is based on measured appliance use profiles detailed in Appendix F. It averages 648 Watts within the conditioned space with a maximum heat gain rate of 1,261 W at 8 PM. Internal heat gains can be reduced by choosing a more efficient refrigerator, compact fluorescent lighting and locating the hot water tank, clothes washer, clothes dryer and freezer outside the conditioned interior. We estimate the combined reduction of these measures to the internal heat gain rate to be approximately 30%. The cost of this measure is difficult to estimate since the major reason for the change out to a more efficient refrigerator or high efficiency lighting is primarily attributable to the direct energy savings of these measures. As a conservatism, however, we assume that one third of the cost is due to the objective of reducing waste heat in the building's interior. For the more efficient refrigerator and lighting this comes to approximately $125.
As expected simulation analysis showed this measure to decrease cooling energy use (-9%) while increasing space heating energy use (+19%). In absolute terms, however, overall space conditioning energy use dropped by 307 kWh or 6% of annual consumption. Obviously, this option will appear more effective when analyzed in a home with a higher heating system efficiency such as a heat pump.
Infiltration Control
Conservative estimates were made for the energy related savings of infiltration control. We assume that caulking, weatherstripping and attention to window and door seals and ceiling and wall penetrations can reduce the building infiltration rate from 0.40 air changes per hour (ACH) by 10% to 0.36 ACH. The small level of reduction is due to the low level of natural driving forces for infiltration in the Florida climate. Although Florida homes are generally leaky, relative to those in more northerly climates, previous studies of wind and thermal buoyancy induced air infiltration in using SF6 tracer gas dilution have found air change rates commonly in the range of 0.1 to 0.3 ACH (Cummings et al., 1991).
The higher air change assumed in the simulations (0.4 ACH) is due to the operation of the air handler in terms of duct leakage and differential pressures within rooms. These are forces that are not as affected by envelope sealing methods. Greater levels of air tightness were not deemed appropriate since this could result in an unacceptably low ventilation rate. This could have serious implications for indoor air quality. The measure was assumed to have a cost of $200, mainly for labor associated with the increased attention to sealing detail with caulking and weatherstripping (Cummings, et. al., 1989). Our simulation analysis showed modest savings (2%) for heating and cooling associated with this measure. Results were similar for existing and new housing.
Wall Insulation and Color
The influence of wall insulation and color on space heating and cooling consumption was modeled as follows: For new buildings, the assumed insulation levels were R-3 on the interior for concrete block and R-11 for frame walls with 2 x 4" studs 16 inches on center. The analysis for existing homes assumes no insulation and concrete block walls. The base case building, both for existing and new structures was assumed to be a light tan color with an effective solar absorptance of 0.6. White walls were assumed to have an effective solar absorptance of 0.3. Parametric runs were performed for both concrete block and frame walls for new construction. Insulation improvements for new housing consisted of R-19 insulation for frame walls with 2 x 6" studs, 24-inches on center. New CBS homes had R-11 insulation on the interior or exterior analyzed as potential improvements. No incremental cost was assumed for painting the walls white versus other colors. Cost for the various insulation improvements are taken from Cummings (1988). Values were checked against cost data assembled in Appendix C.
Simulation analysis results showed a similar magnitude for the annual heating and cooling energy savings for white walls vs. increased wall insulation for new construction (2%). Savings for white walls was greater for uninsulated existing CBS structures (5%).
Concrete Block Construction
A concrete block prototype was created for analysis of new CBS housing. Eight-inch concrete blocks were assumed with a stucco finish and R-3 insulation on the interior with 1/2" sheetrock facing inside. We also examined the addition of R-11 insulation to the interior and exterior. Externally insulated masonry wall construction can provide an inherent thermal storage capability. Both simulation models and empirical research suggest that such exterior insulation schemes will result in lower thermal loads (Fairey et al., 1986, Al-Mofeez and Woods, 1991; Ternes, 1992). Other measures, such as landscape shading and wall color were examined for the block construction case to determine specific differences in influence. The impact of white walls was performed by assuming the white paint with an absorptance of 0.3 was used. Landscape shading assumed that 25% of the walls would be shaded from a newly installed landscape; 67% would be shaded with full tree canopies.
Simulation analysis showed a modest energy reduction associated with R-11 interior insulation (3%), where as exterior R-11 wall insulation was found to be quite effective (10% reduction in heating and cooling loads). White exterior walls provided a 3% reduction in overall heating and cooling loads.
8. Potential Limitations to Realized Savings
A number of considerations may undermine the potential savings available from the described measures for the reconstruction effort. Obviously, lack of concern and apathy towards the overall objective of reducing energy use in the reconstruction is a fundamental obstacle. Many of those rebuilding may not elect to participate in such a program. However, even for well intentioned participants, other factors may exact limitations on realized savings.
Often when energy-efficiency programs do not deliver the expected level of savings, life-style effects are blamed for the shortfall (Davis and Adams, 1988). "Take-back," "snap-back" and "rebound" are all terms that refer to the tendency for consumers to adjust over time to perceived changes in the cost of energy services generated by improvements in energy efficiency. These changes are also known by the micro-economic description of "temporary price elasticity." For example, energy savings due to an air conditioning efficiency program could induce customers to reduce their thermostat setting to increase comfort to a level that they could not previously afford. This diminishes the potential energy savings of the measure. The reality of this fact was observed in a Florida utility study of energy efficient homes, which found the measured summertime thermostat setting of the efficient houses to be 2 - 3oF cooler than the group of conventional residences (Gulf Power Company, 1987). However, "take-back" can also be expressed in other ways, such as more use of air conditioning rather than natural ventilation, increased use of hot water, increased hours of outdoor lighting and so on. Unfortunately, the magnitude of this phenomenon remains poorly researched.
Recent field studies by EPRI of an advanced heat pump lends credence to the theory that "lifestyle" is often expressed as thermostat settings. Thermostat behavior can vary greatly from one home to the next (Lutz, 1992). In the EPRI research differences in the individual thermostat settings in 30 homes being tested accounted for almost all of the variation between the predicted and actual performance of the systems (Kesselring and Lannus, 1991). Use of the DOE 2.1 simulation with the base frame building prototype, showed that a 2oF change in summertime thermostat setting could be expected to alter space cooling energy consumption by approximately 24%. To the extent that "take-back" of comfort is expressed as a changed thermostat setting in response to increased efficiency, we could expect space conditioning savings to be degraded by a like amount. Figure 7 illustrates the sensitivity of the calculated space conditioning loads to increases (heating) or decreases (cooling) to the thermostat setpoint.

Regardless of the immediate reality of the take-back phenomenon, recent studies suggest that its effects may be temporal in many cases, with building owners eventually becoming sensitive once more to utility costs after memory of the alteration fades (Weihl et al., 1988; Keating, 1990).
The relative persistence of savings from energy efficiency measures is another consideration. Service related measures, such as air conditioner tune-ups, may quickly decline in performance whereas others, such as roof coatings, may slowly degrade over a 15-year period. White colored walls may be repainted a darker color. Loss of anticipated savings may be acute in rental properties with equipment installed that requires an informed occupant, such as with a programmable thermostat (Uhlaner and Armstrong, 1991). Still other measures, such a high-efficiency air conditioner change-outs, may experience short-term consumer take-back, with increased savings over the long-run as homeowners realize that monthly utility costs are still sensitive to the degree of use (Rochester Gas and Electric, 1988).
We conclude that while "take-back" and "savings persistence" may
reduce the realized savings of some of the described measures, it is
not a significant enough problem to undermine the more cost-effective
options described in this report. Obviously, however, further research
on this elusive phenomenon is desirable in order to assure available
efficiency savings with greater certainty.
9. Analysis of Technical Savings Potential
Most energy efficiency improvements that reduce air conditioning loads behave according to a law of diminishing returns. The fundamental characteristic is one of decreasing savings associated with each increment designed to reduce building or machine loads. As a result, we analyzed the incremental savings associated with each measure for both new and existing structures using optimization by steepest descent. This means that the measure with the greatest savings is chosen first and implemented in the base case building before re-evaluating the measures for the next choice. Where multiple, competing measures existed (such as with windows), the highest performance option was chosen first to the exclusion of the remaining options associated with the same component. In this way, it is possible to determine a "technical optimum" series of measures. Tables 9 and 10 show the technical optimization process for new and existing homes, respectively. The results are illustrated in Figures 8 and 9.
The technical potential for energy savings in new South Florida homes showed that up to 72% (3,866 kW) of annual heating and cooling electricity consumption could be avoided through incorporation of the fifteen most effective measures. Peak heating and cooling electricity demand could be feasibly reduced by 74% (3.0 kW)